Bussmann ECSR.8 Current Limiting Time Delay Fuse, 0.8 A, 600 V, 200 kA Interrupt, RK5 Class, Cartridge Body

NOTICE: This item has been flagged as discontinued. Limited stock may be available. Please note that this item is subject to removal from your order if it is unfulfillable.
Short Description

These fuses are recommended for AC power distribution system mains, feeders and branch circuits having inductive loads (motors, transformers) or non-inductive loads (lighting, heating) where the available short-circuit current does not exceed 200000 RMS symmetrical amps. These "dual-element, time delay" fuses have minimum industry standard time delay of 10 s at 5 times the fuse rating (8 s minimum for 250 V, 30 A and less). The time delay characteristics of these fuses typically allows them to be sized closer to the running ampacity of inductive loads to reduce cost and provide improved overcurrent protection. These fuses will override normal equipment current surges to reduce unnecessary fuse openings. They are the most popular fuses used in the industry and the most economical for most applications, especially motors and transformers. They have moderate current limitation.

Bussmann Time Delay Fuse, Current Limiting, Series: ECSR, Indicating/Non-Indicating: Non-Indicating, 0.8 A, 600 V, 200 kA Interrupt, Class: RK5, 10 s Response, Ferrule Terminal, Holder Mount, Cartridge Body Type, Dual Element
MFG #: ECSR.8

EECO #: BUECSR.8

Brand: Bussmann
UPC #: 782634508076
Discontinued
Attributes
Features
Documents
Product Information
Attributes
Class
RK5
UNSPSC
39121606
Application
AC Power Distribution System Mains, Feeders and Branch Circuit, Protection of Motors and Motor Branch Circuit, Protection of Transformers and Other Inductive Loads, General Purpose, Lighting, Heating and Other Non-Inductive Loads, Safety and Security Systems
Mounting Type
Holder
Response Time
10
Terminal Type
Ferrule
Voltage Rating
600
Type
Current Limiting
Series
ECSR
Warranty
12 months
Amperage Rating
0.8
Features
  • True dual element construction allows sizing of 125% FLA for motor backup protection
  • Superior overload and cycling capabilities
  • Current limiting provides component short circuit protection
  • Provides motor overload, ground fault and short circuit protection
  • Helps protect motors against burnout from 1-phasing on 3 ph systems
  • The time delay characteristics of these fuses typically allows them to be sized closer to the running ampacity of inductive loads to reduce cost and provide improved over current protection
  • These fuses will override normal equipment current surges to reduce unnecessary fuse openings
  • Dual element fuses can be applied in circuits subject to temporary motor overloads and surge currents to provide both high performance short circuit and overload protection
  • The overload element provides protection against low level over current of overloads and will hold an overload which is five times greater than the ampere rating of the fuse for a minimum of 10 s
  • 10 s minimum at 500% of ampere rating response time