Bussmann ECNR12 Current Limiting Time Delay Fuse, 12 A, 250 VAC/125 VDC, 200 kA Interrupt, RK5 Class, Cartridge Body

Short Description

Edison's UL Class RK5 dual-element, time-delay fuses provide economical solutions to overcurrent protectioni. Available in both 250Vac and 600Vac, with 200kA RMS Sym interrupting ratings and sizes ranging from 0 to 600 amp.

Bussmann Time Delay Fuse, Current Limiting, Series: ECNR, Indicating/Non-Indicating: Non-Indicating, 12 A, 250 VAC/125 VDC, 200 kA Interrupt, Class: RK5, 8 s at 500% Response, Ferrule Terminal, Holder Mount, Cartridge Body Type, Dual Element, 0.56 in Dia x 2 in L Body Size
MFG #: ECNR12

EECO #: BUECNR12

Brand: Bussmann
UPC #: 782634507291
Attributes
Features
Documents
Product Information
Attributes
Class
RK5
UNSPSC
39121606
Material
Fiberglass
Application
AC Power Distribution System Mains, Feeders and Branch Circuit, Protection of Motors and Motor Branch Circuit, Protection of Transformers and Other Inductive Loads, General Purpose, Lighting, Heating and Other Non-Inductive Loads, Safety and Security Systems
Mounting Type
Holder
Response Time
8 s at 500%
Terminal Type
Ferrule
Voltage Rating
250 VAC/125 VDC
Type
Current Limiting
Series
ECNR
Amperage Rating
12
Features
  • True dual element construction allows sizing of 125% FLA for motor backup protection
  • Superior overload and cycling capabilities
  • Current limiting provides component short circuit protection
  • Provides motor overload, ground fault and short circuit protection
  • Helps protect motors against burnout from 1-phasing on 3 ph systems
  • The time delay characteristics of these fuses typically allows them to be sized closer to the running ampacity of inductive loads to reduce cost and provide improved over current protection
  • These fuses will override normal equipment current surges to reduce unnecessary fuse openings
  • Dual element fuses can be applied in circuits subject to temporary motor overloads and surge currents to provide both high performance short circuit and overload protection
  • The overload element provides protection against low level over current of overloads and will hold an overload which is five times greater than the ampere rating of the fuse for a minimum of 10 s
  • 8 s minimum at 500% of ampere rating response time