EATON 15HCL-175E Type HCL E-Rated Medium Voltage 2-Barrel Current Limiting Fuse, 175 A, 15.5 kV, 63 kA Interrupt, Class: E

Short Description

Current limiting E-Rated medium voltage fuses are defined by their melting time-current characteristic that permit their electrical interchangeability with other fuses of the same E Rating. They are physically dimensioned for easy installation in existing hardware to provide positive interruption even on low fault currents. E-Rated fuse constructions are available in ferrule, bolt-on and clip-lock and specialty mount fuses for AMPGARD motor starters Outdoor rating available on select catalog numbers and open fuse indicator speeds troubleshooting by providing a positive visual indication of fuse operation.

EATON Current Limiting Fuse, Type HCL E-Rated Medium Voltage 2-Barrel, 175 A, 15.5 kV, 63 kA Interrupt, Class: E, 50/60 Hz, 600 s Response, 3 in W x 3 in H Body Size
MFG #: 15HCL-175E

EECO #: BU15HCL175E

Brand: Eaton
UPC #: 051712526661
Attributes
Features
Documents
Product Information
Attributes
Class
E
UNSPSC
39121628
Application
Medium Voltage Feeder Circuit Protection, Medium Voltage Metal-Enclosed Switchgear, Medium Voltage Transformer Primary Protection, Medium Voltage Switches and Indoor Applications
Response Time
600
Voltage Rating
15.5
Frequency Rating
50/60
Type
Type HCL E-Rated Medium Voltage 2-Barrel
Series
HCL
Amperage Rating
175
Features
  • Current limiting e-rated medium voltage fuses are defined by their melting time-current characteristic that permit their electrical interchangeability with other fuses of the same e-rating
  • E-rated fuses must have a defined current response time specified by ANSI C37.46
  • E-rated fuses greater than 100 A must melt in 600 s at an RMS current within the range of 220% to 264% of the fuse's nameplate current rating
  • E-rated fuses are physically dimensioned for easy installation in existing hardware
  • Current limiting fuses provide positive interruption even on low fault currents
  • The fuse limits the magnitude of electromechanical stresses in the protected apparatus
  • Open fuse indicator speeds troubleshooting by providing a positive visual indication of fuse operation
  • HCL clip-lock version
everwhere