Appleton® UNILETS® EYF350-AL Dust-Ignitionproof Explosionproof Raintight Conduit Sealing Fitting, 3-1/2 in, For Use With IMC/Threaded Rigid Metallic Conduit, Almag 35 Aluminum, Epoxy Powder Coated

Short Description

Ensure maximum safety and reliability with the Appleton® UNILETS® EYF350-AL Dust-Ignitionproof Explosionproof Raintight Conduit Sealing Fitting. Designed for use with IMC and threaded rigid metallic conduit, this durable fitting is crafted from Almag 35 aluminum and features an epoxy powder coating for enhanced protection. Perfect for demanding environments!Enhanced by AI

Appleton® UNILETS® Conduit Sealing Fitting, Dust-Ignitionproof Explosionproof Raintight, Series: EY Series, 3-1/2 in, For Use With: IMC/Threaded Rigid Metallic Conduit, Almag 35 Aluminum, Epoxy Powder Coated, 8.94 in L x 4.75 in W

MFG #: EYF350-AL

EECO #: APEYF350AL

Brand: Appleton
UPC #: 781381600071
Attributes
Features
Documents
Product Information
Attributes
Finish
Epoxy Powder Coated
UNSPSC
39121311
Material
Almag 35 Aluminum
Application
For prevent passage of gases, vapors or flames from one portion of conduit system to another
Size
3-1/2
Type
Dust-Ignitionproof Explosionproof Raintight
Series
EY Series
Warranty
Limited
Dimensions
8.94 in L x 4.75 in W
Suitable For Use With
IMC/Threaded Rigid Metallic Conduit
Features
  • Smooth, rounded integral bushing in each hub to protect conductor insulation
  • Accurately tapped, tapered NPT threads for tight, rigid joints and ground continuity
  • Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub
  • Restrict any explosion to the sealed off enclosure
  • Required in Class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures
  • Required in Class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps
  • Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location
  • Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit, seal must be located within 18 in of either enclosure
  • Required where cables which exceed rate of gas or vapor transmission permitted for seals are used in Class I, Division 2 locations
  • 25% fill vertical and horizontal conduit sealing fittings for close turning radius