Appleton® UNILETS® ESUM50 Dust-Ignitionproof Explosionproof Raintight Conduit Sealing Fitting With Removable Male Nipple, 1/2 in, For Use With IMC/Threaded Rigid Metallic Conduit, Malleable Iron, Triple Coated

Short Description

These sealing fittings minimizes the passage of gases and vapors and prevents the passage of flames from one portion of a conduit system to another. They prevent pressure piling within the conduit system and contain any explosion that occurs. The ESU Series provides a pouring spout that rotates 90 deg for sealing vertical or horizontal conduit.

Appleton® UNILETS® Conduit Sealing Fitting, Dust-Ignitionproof Explosionproof Raintight, Series: ESUM, 1/2 in, For Use With: IMC/Threaded Rigid Metallic Conduit, Malleable Iron, Triple Coated, 3 in L x 2.94 in W
MFG #: ESUM50

EECO #: APESUM50

Brand: Appleton
UPC #: 781381306751
Attributes
Features
Documents
Product Information
Attributes
Finish
Triple Coated
UNSPSC
39121311
Material
Malleable Iron
Application
For prevent passage of gases, vapors or flames from one portion of conduit system to another
Size
1/2
Type
Dust-Ignitionproof Explosionproof Raintight
Series
ESUM
Warranty
Limited
Dimensions
3 in L x 2.94 in W
Suitable For Use With
IMC/Threaded Rigid Metallic Conduit
Features
  • Smooth, rounded integral bushing in each hub to protect conductor insulation
  • Accurately tapped, tapered NPT threads for tight, rigid joints and ground continuity
  • Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub
  • For sealing vertical or horizontal conduit
  • Pouring spout rotates 90 deg
  • Removable cover provides full access for damming 1/2 in thru 1 in sizes have threaded cover openings for damming
  • Restrict any explosion to the sealed off enclosure
  • Required in Class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures
  • Required in Class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps
  • Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location
  • Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit
  • Seal must be located within 18 in of either enclosure
  • Required where cables which exceed rate of gas or vapor transmission permitted for seals are used in Class I, Division 2 locations
  • Chromate/epoxy powder coated/zinc electroplated finish